BWR3067ASi Safety PCB Module, 43 mm x 30 mm

Product description

ASi Safety PCB Module, 43 mm x 30 mm, 1 x 2 channels safe input (SIL 3, cat. 4) for floating contacts, 2 digital outputs, input voltage/sensor supply out of ASi, output voltage/actuator supply out of ASi, max. 20 mA per output, periphery connection via connecting wires (200 mm), thick coated, LED, ASi connection via connecting wires (200 mm), 1 single address

Technical data

Circuit board dimensions 43 mm x 30 mm
Inputs Safety

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.


Suitable for applications up to category 4/PLe/SIL 3.

1 x 2 channels
Outputs digital 2 x electronic
Outputs Safety

Suitable for applications up to category 4/PLe/SIL 3.

no local safe output
Safety signal inputs floating contacts
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of ASi
PCB connection

Connection possible via wiring pins, screw terminals, solder lugs or connecting wires.

Further connection options are available on request.

connecting wires, 200 mm
Coating

Coating protects components and circuit boards when touched. Thick coated and thin coated are available.
 

thick coated
ASi connection

The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

connecting wires, 200 mm

How to troubleshoot an existing ASi installation