BWU3608Active Distributor ASi, IP67, 4I
Product description
Active Distributor ASi, IP67, housing depth 35 mm, 4 digital inputs, input voltage/sensor supply out of AUX, periphery connection via 3 x round cable/connecting wires and 1 M8 cable socket, straight, 4 poles, cable length 1 m, flat design, installation in cable duct possible (installation depth >35 mm), LED, connections for 1 x ASi profile cable, ASi connection via profile cable and piercing technology, 1 AB address
Technical data
Inputs digital | 4 |
Outputs digital | no digital outputs |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of AUX |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | no output voltage |
Connection | 1 x M8 cable socket, straight, 4 poles, 3 x round cable/connecting wires |
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | 1 m |
Flat design, installation in cable duct possible
Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation. | yes, depth: 35 mm |
ASi address
Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted. | 1 AB address |
Special function | no special function |