BWU4974Active Distributor ASi-5 Motor Module for Lenze i550 motec frequency inverter, IP67, 1M

Product description

Active distributor ASi-5 motor module, IP67, housing depth 35 mm, for 1 x Lenze i550 motec frequency inverter with Modbus TCP interface,  periphery connection via 1 x M12 cable plug, D coded, straight, 4 poles, cable length 1 m, flat design, installation in cable duct possible (installation depth > 35 mm), LED, connection for 1 x ASi profile cable, ASi connection via profile cable and piercing technology, 1 ASi-5 address

Technical data

Type Active distributor ASi-5 motor module
ASi-5/ASi-3

The device communicates via the standard ASi-3 and/or ASi-5.

ASi-5 compatible
Housing depth: 35 mm
Protection rating

"IP20":
Protected against solid foreign bodies having a diameter of 12.5 mm or larger and against finger contact, not protected against water.


"IP40":

Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water.

"IP54":

Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.


"IP65":
Dust-tight, full protection against contact, protection against spray water (jet) from any angle.

"IP67":

Dust-tight, full protection against contact, protection against temporary immersion.

IP67
Number of Drives 1
Line protection fuse

"yes":

In the motor module UL approved fuses are placed before each of the motor supply connections. A short circuit in the motor causes this fuse to blow, protecting the connection cable between the module and motor.

After blowing the not exchangeable fuse the module is no longer functional and the module needs to be replaced. The characteristics of the fuse must be checked against the motor data before using the module.

The protection circuit in the module allows a very simple protection of the motor cables. The fuse for the cable protection is a slow-blow one; without short circuit the robust behavior of the module remains.


"no":

The motor module is designed to supply the 24 V directly to the motor. At high currents or surges as they occur for example at braking, the module will not be damaged.

The cable protection should be realized outside the motor module with additional measures.

no
Flat design, installation in cable duct possible

Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation.

yes, depth: 35 mm
Inputs digital no digital inputs
Outputs digital no digital outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

no output voltage
Connection 1 x M12 cable plug, D coded, straight, 4 poles
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

1 m
ASi connection

The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

ASi profile cable
Required Master profile

Required profile that the ASi master needs to have in order to connect and operate the module.

M5
ASi node profile

The node profiles allow numerous quickly configurable settings to be made on the module in order to optimally support the connected peripherals in most applications. The easiest way to select the node profiles is via the PC software.

If ID1 is in brackets (), this means it is the changeable default value; if ID1 is without brackets, it means it is a fixed, unchangeable value.

depending on configuration
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation

Manuals