BWU4722ASi-5 Cable Duct Motor Module, IP54, M8 for 24 V motorized rollers, 2M/2I

  • Control and supply of 2 x 24 V motorized rollers
  • E.g. Interroll EC5000 AI, 24 V, 20 W/35 W, Itoh Denki PM500XC/XK, Rulmeca RDR BL-3
  • Cyclic writing of speed and ramps possible
  • Line protection fuse, separately for each motor 5,0 A
  • Logo_ASi-5
  • Logo_cULus
  • Logo_CE

Product description

ASi-5 Cable duct motor module in IP54, with 4 x M8 cable sockets for 2 x 24 V motorized rollers e.g. Interroll (EC5000 AI, 24 V, 20 W/35 W), Itoh Denki (PM500XC/XK), Rulmeca (RDR BL-3), 2 digital inputs, input voltage/sensor supply out of ASi, output voltage/actuator supply out of AUX, internal line protection, separately for each motor 5,0 A (slow-blow fuse), flat design, installation in cable duct possible (installation depth ≥ 18 mm), periphery connection via 2 x M8 snap-in cable sockets, straight, 5 poles (drives) and 2 x M8 snap-in cable sockets, straight, 4 poles (sensors), cable length of motor connections 0,4 m, cable length of input connections 0,06 m, ASi connection via profile cable and piercing technology, 1 ASi-5 address

Technical data

Drive

If you cannot find your drive, please do not hesitate to contact us. Bihl+Wiedemann creates customized drive solutions with ASi for motorized rollers, DC motors and frequency inverters.

Interroll EC5000 AI, 24 V (20 W/35 W), Itoh Denki PM500XC/XK, RULMECA RDR BL-3
Number of Drives 2
Inputs digital 2
Outputs digital no digital outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi and out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
Connection 2 x M8 cable sockets, straight, 4 poles, 2 x M8 snap-in cable sockets, straight, 5 poles
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

M: 0,40 m, I: 0,06 m
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation

Manuals