BWR1801ASi Safety PCB Module, 73 mm x 37,5 mm, 1SI/2O, wiring pins, angled

  • Logo_ASi
  • Logo_UR
  • Logo_CE

Product description

ASi Safety PCB Module, 73 mm x 37,5 mm, 1 x 2 channels safe input (SIL 3, cat. 4) for floating contacts, 2 digital outputs, input voltage/sensor supply out of ASi, output voltage/actuator supply out of AUX, periphery connection via wiring pins, angled, LED, 1 single address

Technical data

Type circuit board 73 mm x 37,5 mm, Safety
Circuit board dimensions 73 mm x 37,5 mm
Inputs digital no digital inputs
Outputs digital 2 x electronic
Inputs analog no analog input
PCB connection

Connection possible via wiring pins, screw terminals, solder lugs or connecting wires.

Further connection options are available on request.

wiring pins, angled
Coating

Coating protects components and circuit boards when touched. Thick coated and thin coated are available.
 

no
LED status display

Display of the status of the inputs/outputs, ASi communication or peripheral errors and the status of the AUX supply according to the ASi specification.

yes
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 Single address

How to troubleshoot an existing ASi installation