BWU3408Passive Distributor ASi/AUX to 1 x M12 cable socket, angled, 5 poles, depth 19 mm, IP67
Product description
Passive Distributor ASi/AUX, housing depth 19 mm, IP67, connections for 1 x ASi and 1 x AUX profile cables to 1 x M12 cable socket, angled, 5 poles, cable length 1 m, flat design, installation in cable duct possible (installation depth ≥ 19 mm)
Technical data
Type | Passive distributor ASi/AUX |
Profile cable connection
The module has connections for ASi and/or AUX profile cables to supply data and (auxiliary) power. Depending on the design, the devices also have an integrated profile cable derivation. | 1 x ASi, 1 x AUX 24 V |
Connection | 1 x M12 cable socket, angled, 5 poles |
Internal fuse
Interchangeable, self-resetting or slow-blow fuses are available. | no |
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | 1 m |
Flat design, installation in cable duct possible
Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation. | yes, depth: 19 mm |
Housing | depth: 19 mm |
LED status display
Display of the status of the inputs/outputs, ASi communication or peripheral errors and the status of the AUX supply according to the ASi specification. | no |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP67 |
Special function | to connect ASi devices via M12 |