BWU1964ASi Analog Input Module, IP65, M12, 2AI (0…10V)
There is a successor to this article → BWU3102
The successor is not recommended for use as a spare part - Conditions for Selecting and Using the Successor Model
Product description
ASi Analog Input Module in IP65, width 45 mm, with 2 x M12 sockets, 2 analog inputs (0…10 V), signal at pin2/pin4, input voltage/sensor supply out of ASi, periphery connection via 2 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 single address
The substructure module is not included in the scope of delivery.
Technical data
Inputs digital | no digital inputs |
Outputs digital | no digital outputs |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of ASi |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | no output voltage |
Connection | 2 x M12 sockets, 5 poles |
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | no |
ASi address
Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted. | 1 Single address |