BWU4230ASi-5 Self-configuring I/O Module, IP67, M12, 16I/O

  • Logo_ASi-5
  • Logo_cULus
  • Logo_CE

Product description

ASi-5 self-configuring I/O module, in IP67, with 8 x M12 sockets, up to 16 digital inputs, up to 16 digital outputs, Y/mixed wiring, input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, periphery connection via 8 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 ASi-5 address


The substructure module is not included in the scope of delivery.

Technical data

Drive

If you cannot find your drive, please do not hesitate to contact us. Bihl+Wiedemann creates customized drive solutions with ASi for motorized rollers, DC motors and frequency inverters.

Lenze Smart Motor, SEW MOVI-SWITCH 2S, SEW MOVIMOT
Number of Drives depending on configuration
Inputs digital up to 16, depending on configuration
Outputs digital up to 16 x electronic, depending on configuration
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
Connection 8 x M12 sockets, 5 poles
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

no
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation

Manuals

    Device Description Files (GSD, EDS, ESI, SDD, etc.)


    Frequently bought together

    ASi-5 Self-configuring I/O Module, IP67, M12, 16I/O
    BWU4230
    Your price-
    List price-
    ASi Substructure Module in IP67
    BWU2351
    Your price-