BWU4088Active Distributor ASi-5/IO-Link Master with 1 Port, IP67, M12, 1 IO-Link Port Class B

Product description

Active Distributor ASi-5/IO-Link Master, IP67, housing depth 35 mm, 1 x IO-Link port class B (1 x C/Q), sensor supply (IO-Link supply and input/output supply) out of AUX, actuator supply out of AUX, periphery connection via 1 x M12 cable socket, straight, 5 poles, cable length 1 m, flat design, installation in cable duct possible (installation depth >35 mm), LED, connections for 1 x ASi and 1 x AUX profile cables, ASi connection via profile cable and piercing technology, 1 ASi-5 address

Technical data

Drive

If you cannot find your drive, please do not hesitate to contact us. Bihl+Wiedemann creates customized drive solutions with ASi for motorized rollers, DC motors and frequency inverters.

Lenze i550 Protec
Number of Drives 1
Inputs digital 1 x IO-Link Port
Outputs digital 1 x IO-Link Port
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
Connection 1 x M12 cable socket, straight, 5 poles
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

1 m
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation

Manuals

    Device Description Files (GSD, EDS, ESI, SDD, etc.)