BWR4263ASi-5 PCB Module, 140 mm x 40 mm, self-configuring 32I/O, wiring pins, straight

Product description

ASi-5 PCB Module, 140 mm x 40 mm, up to 32 digital inputs, up to 32 digital outputs, input voltage/sensor supply out of 24 VDC ext., output voltage/actuator supply out of AUX, max. 350 mA per output, periphery connection via wiring pins, straight, LED, ASi connection via wiring pins, straight, 1 ASi-5 address

Technical data

Type circuit board 140 mm x 40 mm, ASi-5
Circuit board dimensions 140 mm x 40 mm
Inputs digital up to 32, depending on configuration
Outputs digital up to 32 x electronic, depending on configuration
Inputs analog no analog input
PCB connection

Connection possible via wiring pins, screw terminals, solder lugs or connecting wires.

Further connection options are available on request.

wiring pins, straight
Coating

Coating protects components and circuit boards when touched. Thick coated and thin coated are available.
 

no
LED status display

Display of the status of the inputs/outputs, ASi communication or peripheral errors and the status of the AUX supply according to the ASi specification.

yes
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

external 24VDC
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation

Manuals

    Device Description Files (GSD, EDS, ESI, SDD, etc.)