BWU2330ASi-3 PROFINET Gateway with integrated Safety Monitor, 2 ASi masters
There is a successor to this article → BWU3080
The successor is not recommended for use as a spare part - Conditions for selecting and using the successor
Product description
ASi-3 PROFINET Gateway with integrated Safety Monitor, 2 ASi masters, 4 digital inputs, expandable to max. 62 x 2 channels safe inputs, 4 release circuits (2 x relay outputs and 2 x electronic safe outputs), expandable to max. 16 safe outputs, diagnostic and configuration via PROFINET or RS232 diagnostic interface, duplicate address recognition, ASi fault detector, IP20
Technical data
Type | Safety, PROFINET |
Model | Gateway with integrated Safety Monitor |
ASi-5/ASi-3
The device communicates via the standard ASi-3 and/or ASi-5. | ASi-3 compatible |
ASi Safety
The device communicates safely via the standard ASi-3 Safety and/or ASi-5 Safety. | ASi-3 Safety capable |
Inputs Safety
Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.
| no local safe inputs |
Inputs digital, EDM
An externally connected relay (contactor) can be monitored by connecting the feedback loop to the EDM input. | 4 |
Outputs Safety
Suitable for applications up to category 4/PLe/SIL 3. | 4 release circuits, 2 x relay, 2 x electronic safe outputs |
Safety communication | no Safety communication |
Fieldbus interface
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. Bihl+Wiedemann offers a wide range of gateways for common fieldbus interfaces:
| PROFINET |
Number of ASi networks, number of ASi Master
Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | 2 ASi networks, 2 ASi-3 Masters |
Integrated decoupling, ASi current measurement in the gateway
" yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | no, max. 8 A/ASi network, redundant supply |
Diagnostic and configuration interface
Access to ASi master and safety monitor via own software from Bihl+Wiedemann using the diagnostic interface (e.g. USB, RJ45, RS232). For certain devices with Ethernet-based fieldbus (PROFINET, EtherNet/IP), there is also the option of diagnostics and configuration directly via the fieldbus interface.
The latest version of the device description file of the gateway/gateway with integrated safety monitor (GSD, GSDML, EDS, etc.) is available in the "Downloads" section of the respective device. | Ethernet fieldbus, RS 232 |
Recognition of duplicate ASi addresses
Detects whether the same address has been assigned to two ASi nodes. Frequent error when using a handheld addressing device. | yes |
ASi fault detector
Checks the ASi line for interference effects such as noise, external voltages, ... | yes |
Programming in C
Using a C-program offers the possibility to run mini-PLC functions with a gateway. | no |
Connection | push in terminals |
ASi connection
The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.
| Push-in terminals |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP20 |
How to get started with Bihl+Wiedemann products
How to easily implement your ASi installation
How to troubleshoot an existing ASi installation
Manuals
EPLAN Macros
Device Description Files (GSD, EDS, ESI, SDD, etc.)
Video Tutorial
- Video Tutorial: Tips & Tricks: Replacing a defective device (DE)
- Video Tutorial: Tips & Tricks: Replacing a defective device (EN)
- Video Tutorial: Tips & Tricks: Replacing a Gateway Using the Chip Card (DE)
- Video Tutorial: Tips & Tricks: Replacing a Gateway Using the Chip Card (EN)
- Video Tutorial: ASIMON360 configuration of Safety devices (DE)
- Video Tutorial: ASIMON360 configuration of Safety devices (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: Online bus information (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: Online bus information (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: Custom catalog (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: Custom catalog (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: How to copy slaves and devices (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: How to copy slaves and devices (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: How to deactivate slaves (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: How to deactivate slaves (EN)
Quick Start Guides
- Quick Start Guide: Tips & Tricks: Replacing a defective device (DE)
- Quick Start Guide: Tips & Tricks: Replacing a defective device (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: Custom catalog (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: Custom catalog (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to copy slaves and devices (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to copy slaves and devices (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to deactivate ASi modules (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to deactivate ASi modules (EN)
- Quick Start Guide: TIA V13 Tool Calling Interface (DE)
- Quick Start Guide: TIA V13 Tool Calling Interface (EN)
- Quick Start Guide: Simatic Manager Standard Diagnosis Online (DE)
- Quick Start Guide: Simatic Manager Standard Diagnosis Online (EN)
- Quick Start Guide: Simatic Manager Diagnosis via Command Interface (DE)
- Quick Start Guide: Simatic Manager Diagnosis via Command Interface (EN)
- Quick Start Guide: Replacing a Gateway with a successor in the TIA Portal (DE)
- Quick Start Guide: Replacing a Gateway with a successor in the TIA Portal (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: Online bus information (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: Online bus information (EN)
- Quick Start Guide: ASIMON360 Configuration of Safety devices (DE)
- Quick Start Guide: ASIMON360 Configuration of Safety devices (EN)
- Quick Start Guide: ASIMON360 Configuration of Safety devices (PL)