BWU3271ASi Safety Thermocouple Module, IP20, 1SI

Product description

ASi Safety Thermocouple Module in IP20, 22,5 mm x 114 mm, with 6 x 4 contacts, 1 x 2 channels safe input (SIL 3, cat. 4) for thermocouples, input voltage/sensor supply out of ASi, periphery connection via Push-in terminals, without limitation of connector cable length (loop resistance 150 Ohm), ASi connection via Push-in terminals, ASi addresses depending on configuration

Technical data

Inputs Safety

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.


Suitable for applications up to category 4/PLe/SIL 3.

1 x 2 channels
Safety signal inputs thermocouples
Outputs Safety

Suitable for applications up to category 4/PLe/SIL 3.

no local safe output
Safety signal outputs no Safety signal outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

no output voltage
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

depending on configuration
Special function no special function

How to troubleshoot an existing ASi installation