BWU2765ASi Motor Module, IP67, M12 for 24V motorized rollers, 2M/2I

Product description

ASi Motor Module in IP67, with 4 x M12 sockets for 2 x 24 V motorized rollers Interroll (EC310) or RULMECA (RDR BL-2), 2 digital inputs, input voltage/sensor supply out of ASi, motor control supply via AUX, internal line protection, separately for each motor 3,5 A (slow-blow fuse), periphery connection via 4 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 AB address

Speed setting via ASi parameters.

In the motor module UL approved fuses are placed before each of the motor supply connections. A short circuit in the motor causes this fuse to blow, protecting the connection cable between the module and motor.

After blowing the fuse the module is no longer functional and needs to be replaced. The characteristics of the fuse must be checked against the motor data before using the module.

The protection circuit in the module allows a very simple protection of the motor cables. The fuse for the cable protection is a slow-blow one; without short circuit the robust behavior of the module remains.

The substructure module is not included in the scope of delivery.

Technical data

Drive

If you cannot find your drive, please do not hesitate to contact us. Bihl+Wiedemann creates customized drive solutions with ASi for motorized rollers, DC motors and frequency inverters.

Interroll EC310, Itoh Denki PM500XC/XK, RULMECA RDR BL-2
Number of Drives 2
Inputs digital 2
Outputs digital no digital outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

no output voltage
Connection 4 x M12 sockets, 5 poles
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

no
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 AB address