BWU3118ASi Safety I/O Module, IP20, 8SI/1SO/16I
Product description
ASi Safety I/O Module in IP20, 22,5 mm x 114 mm, with 6 x 4 contacts, up to 8 x 2 channels safe inputs (SIL 3, cat. 4) for floating contacts or OSSDs, complementary switch, complementary OSSDs, up to 16 standard inputs, 1 release circuit (1 x electronic safe output) augmented reliability, input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, periphery connection via coded push-in terminals, without limitation of connector cable length (loop resistance 150Ω), ASi connection via coded push-in terminals, ASi addresses depending on configuration
Technical data
Type | IP20, 22,5 mm x 114 mm, 6 x 4 contacts, Safety |
Housing | 22.5 mm x 99.0 mm x 114.5 mm, 6 x 4 contacts |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP20 |
Inputs Safety
Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.
| 8 x 2 channels |
Inputs digital, EDM
An externally connected relay (contactor) can be monitored by connecting the feedback loop to the EDM input. | up to 16, depending on configuration |
Outputs Safety
Suitable for applications up to category 4/PLe/SIL 3. | 1 release circuit, 1 x electronic safe output |
Outputs digital | no digital outputs |
Safety signal inputs | OSSDs, complementary OSSDs, complementary switch, floating contacts |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of AUX |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX |
Length of connector cable | unlimited |
ASi connection
The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.
| coded clamps |
ASi address
Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted. | depending on configuration |
Coating
Coating protects components and circuit boards when touched. Thick coated and thin coated are available. | given by housing |
Special function | no special function |
How to get started with Bihl+Wiedemann products
How to easily implement your ASi installation
How to troubleshoot an existing ASi installation
Manuals
Video Tutorial
- Video Tutorial: Tips & Tricks: Replacing a defective device (DE)
- Video Tutorial: Tips & Tricks: Replacing a defective device (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: Online bus information (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: Online bus information (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: Custom catalog (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: Custom catalog (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: How to copy slaves and devices (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: How to copy slaves and devices (EN)
- Video Tutorial: Tips & Tricks in ASIMON360: How to deactivate slaves (DE)
- Video Tutorial: Tips & Tricks in ASIMON360: How to deactivate slaves (EN)
Quick Start Guides
- Quick Start Guide: Tips & Tricks: Replacing a defective device (DE)
- Quick Start Guide: Tips & Tricks: Replacing a defective device (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: Custom catalog (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: Custom catalog (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to copy slaves and devices (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to copy slaves and devices (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to deactivate ASi modules (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: How to deactivate ASi modules (EN)
- Quick Start Guide: Tips & Tricks in ASIMON360: Online bus information (DE)
- Quick Start Guide: Tips & Tricks in ASIMON360: Online bus information (EN)