BWU3144ASi Digital I/O Module EXTREME, IP67, M12, 4I/4O

Product description

ASi Digital I/O Module EXTREME Product Line in IP67, with 8 x M12 sockets, 4 digital inputs, 4 digital outputs, Y wiring, input voltage/sensor supply out of ASi, output voltage/actuator supply out of AUX, periphery connection via 8 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 AB address

100% protection against moisture

High resistance to salt spray

High corrosion resistance to chemically active substances

Assured functionality at extreme temperatures from – 40 °C to 70 °C

Shock resistant to 30 g (11 ms)

Vibration rated for a frequency of 5-500 Hz at an amplitude of 50 mm pp / 6 g

The substructure module is not included in the scope of delivery.

Technical data

Inputs digital 4
Outputs digital 4 x electronic
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
Connection 8 x M12 sockets, 5 poles
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

no
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 AB address