BWU4775ASi-5 Module with integrated IO-Link Master with 4 Ports, IP20, 4 IO-Link Ports/4AI (4...20 mA)

  • Quadruple IO-Link master
  • 4 x IO-Link ports configurable for port class A or port class B
  • Logo_ASi-5
  • Logo_CE

Product description

ASi-5 module with integrated IO-Link Master in IP20, 22,5 mm x 114 mm, with 6 x 4 contacts, 4 x IO-Link ports with configurable connectors for port class A or port class B (4 x C/Q), 4 analog inputs (4...20 mA), sensor supply (IO-Link supply and input/output supply) out of AUX, periphery connection via Push-in terminals, ASi connection via Push-in terminals, 1 ASi-5 address, optimal application in the main control cabinet


Terminal assignment (C/Q, L+, L-, I) compatible with pin assignment of IO-Link port class A (M12).


Connected IO-Link devices with port class B (M12) with a higher current consumption have to be supplied directly via a separate power supply.


Compatible with 3 pole IO-Link devices (M8).

Technical data

Inputs analog 4 x 4 … 20 mA
Outputs analog no analog outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
M8/M12 wiring

Single wiring: 1 input or output per connection.

 

Y wiring: 2 inputs or outputs per connection.

 

Mixed wiring: 1 input and 1 output per connection.

 

Exact pin assignment see data sheet.
 

no M8/M12 wiring
Connection push in terminals
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation