BWU2852Safety Basic Monitor with extended features, 1 ASi-3 master

Product description

Safety Basic Monitor with extended features, 1 ASi-3 master, integrated decoupling, max. 0,5 A/ASi network, max. 8 A with ASi power supply, ASi current measurement, 22.5 mm x 99 mm x 114 mm, with 6 x 4 contacts, 6 digital inputs or 3 x 2 channels safe inputs (SIL 3, cat. 4), input 3 optional for speed monitors (up to 4kHz), expandable to max. 31 x 2 channels safe inputs, 1891 x 2 channels safe inputs in max. configuration, 2 release circuits (2 x electronic safe outputs), expandable to max. 32 safe outputs, 991 safe outputs in max. configuration, Safe Link, diagnostic and configuration via Ethernet diagnostic interface, periphery connection via push-in terminals, ASi/AUX connection via push-in terminals, IP20


Safety compact controller with safety inputs and outputs.

Safety standstill/speed monitor for up to 3 axes.

Ethernet interface.

Technical data

Fieldbus interface

Communication interface between fieldbus and gateway:

interfaces for standardized fieldbus systems in industrial automation. Bihl+Wiedemann offers a wide range of gateways for common fieldbus interfaces:

 

  • PROFIBUS
  • PROFINET
  • EtherNet/IPTM + Modbus TCP
  • BACnet/IP
  • DeviceNet
  • ControlLogix
  • Compact-/MicroLogix
  • EtherCat
  • POWERLINK
  • CC-Link
  • CANopen
  • RS 485 Modbus
  • OPC UA server

 

ASi monitors
Safety communication Safe Link
Model Safety Basic Monitor with extended features
Inputs Safety

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.


Suitable for applications up to category 4/PLe/SIL 3.

3 x 2 channels, input 3 optional for speed monitor (up to 4 kHz)
Outputs Safety

Suitable for applications up to category 4/PLe/SIL 3.

2 release circuits, 2 x electronic safe outputs
Number of ASi networks, number of ASi Master
Standard devices

"Single Master":

1 ASi network, 1 ASi-5/ASi-3 Master.

1 ASi network, 1 ASi-3 Master.

"Double Master":

2 ASi networks, 2 ASi-5/ASi-3 Masters.

2 ASi networks, 2 ASi-3 Masters.

Safety devices

"Single Master" :

1 ASi network, 1 ASi-5/ASi-3 Master.

1 ASi network, 1 ASi-3 Master.

"Double Master" :

2 ASi networks, 2 ASi-5/ASi-3 Masters.

2 ASi networks, 2 ASi-3 Masters.

"Optional ASi Safety coupling circuit" :
2 ASi networks, 1 ASi-3 Master.

1 ASi network, 1 ASi-3 Master
Integrated decoupling, ASi current measurement in the gateway

" yes, max. 4 A/ASi network ":

Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).

Operation with short cable lengths with standard 24 V power supply possible.


" yes, max. 8 A/ASi network ":

Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).

Operation with short cable lengths with standard 24 V power supply possible.


"yes, optimized for 2 x NEC class 2 power supplies"

Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.


"no, max. 8 A/ASi network, redundant supply ":

1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies.

Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.


" no, max. 8 A/ASi network ":

1 ASi power supply per ASi network.

yes, max. 0,5 A/ASi network, max. 8 A with ASi power supply

How to troubleshoot an existing ASi installation

Manuals