BWU4277ASi-5 Safety I/O Module, IP20, 14SI/2SO

Product description

ASi-5 Safety I/O Module in IP20, 22,5 mm x 114 mm, with 6 x 4 contacts, up to 14 x 1 channel safe inputs (SIL1, cat. 2, PLc) or up to 7 x 2 channels safe inputs (SIL 3, cat. 4, PLe) for floating contacts, OSSDs, complementary switch, complementary OSSDs, inputs SI13+SI14 optional as EDM inputs, up to 14 standard inputs, 2 release circuits (2 electronic safe outputs), input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, periphery connection via Push-in terminals, without limitation of connector cable length (loop resistance 150Ω), ASi connection via Push-in terminals, 1 ASi-5 address

Technical data

Housing 22.5 mm x 99.0 mm x 114.5 mm
Protection rating

"IP20":
Protected against solid foreign bodies having a diameter of 12.5 mm or larger and against finger contact, not protected against water.


"IP40":

Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water.

"IP54":

Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.


"IP65":
Dust-tight, full protection against contact, protection against spray water (jet) from any angle.

"IP67":

Dust-tight, full protection against contact, protection against temporary immersion.

IP20
Inputs Safety

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.


Suitable for applications up to category 4/PLe/SIL 3.

14 x 1 channel, 7 x 2 channels
Inputs digital, EDM

An externally connected relay (contactor) can be monitored by connecting the feedback loop to the EDM input.

2 EDM
Outputs Safety

Suitable for applications up to category 4/PLe/SIL 3.

2 release circuits, 2 x electronic safe outputs
Outputs digital no digital outputs
Safety signal inputs OSSDs, complementary OSSDs, complementary switch, floating contacts
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
Length of connector cable unlimited
ASi connection

The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

Push-in terminals
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address
Coating

Coating protects components and circuit boards when touched. Thick coated and thin coated are available.
 

given by housing
Special function no special function