BWU4277ASi-5 Safety I/O Module, IP20, 14SI/2SO
Product description
ASi-5 Safety I/O Module in IP20, 22,5 mm x 114 mm, with 6 x 4 contacts, up to 14 x 1 channel safe inputs (SIL1, cat. 2, PLc) or up to 7 x 2 channels safe inputs (SIL 3, cat. 4, PLe) for floating contacts, OSSDs, complementary switch, complementary OSSDs, inputs SI13+SI14 optional as EDM inputs, up to 14 standard inputs, 2 release circuits (2 electronic safe outputs), input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, periphery connection via Push-in terminals, without limitation of connector cable length (loop resistance 150Ω), ASi connection via Push-in terminals, 1 ASi-5 address
Technical data
Housing | 22.5 mm x 99.0 mm x 114.5 mm |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP20 |
Inputs Safety
Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.
| 14 x 1 channel, 7 x 2 channels |
Inputs digital, EDM
An externally connected relay (contactor) can be monitored by connecting the feedback loop to the EDM input. | 2 EDM |
Outputs Safety
Suitable for applications up to category 4/PLe/SIL 3. | 2 release circuits, 2 x electronic safe outputs |
Outputs digital | no digital outputs |
Safety signal inputs | OSSDs, complementary OSSDs, complementary switch, floating contacts |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of AUX |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX |
Length of connector cable | unlimited |
ASi connection
The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.
| Push-in terminals |
ASi address
Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted. | 1 ASi-5 address |
Coating
Coating protects components and circuit boards when touched. Thick coated and thin coated are available. | given by housing |
Special function | no special function |